Test Objects
What are test objects?
Test objects are the distribution boxes or cables with sockets, connector outlets or inlets that can be tested by the EST.
| Distribution Box | Cable |
|---|---|
![]() | ![]() |
To correctly describe the test objects, we need to define the following terms:
- Outlet, female panel mounted connection
- Inlet, male panel mounted connection
- Connector, female cable mounted connection
- Plug, male cable mounted connection
Cable
A cable suitable for testing with the EST has one Connector and one Plug. There are no active components in the cable, and it is not connected to any power source.
For cables, the EST tests the correct wiring, the resistances of the wires and the insulation resistance.
If required, the EST can also check deviation of resistances between the wires, which can indicate a potential problem with the cable.
Distribution box
A distribution box suitable for testing with the EST is a passive power distribution box with one Inlet and one or more Outlets or Connectors. There can be active components in the distribution box and it is not connected to any power source.
What are not test objects?
The EST is designed to test passive distribution boxes or cables using a high density of available connections. Due to this the maximum test and supply current is limited. Testing appliances or machines with the EST is not possible, as these often require a higher test current and have active components. For those we recommend an Applicance Tester, often called PAT tester.
How does this limit the use of the EST?
Distribution boxes with active components, such as contactors or undervoltage lockouts, cannot be tested with the EST without modification. Test Objects may be modified to be suitable for testing with the EST, for example by bypassing or disabling the active components.
Example of such modifications include disconnects for phase indicator lights or fans inside the distribution box.
These may inhibit insulation resistance testing, but they do not pose a safety risk.
When modifying test objects, it is important to ensure that the modifications do not affect the compliance to regulations.
The EST only tests the electrical safety of the components that are defined in the test object definition.
Test coverage of all components is the responsibility of the user.
Archiving (delete)
To maintain consistency of the test results and related serial numbers, you cannot delete test objects. However, you can archive them to hide them from the list of active test objects.
Restoring
Archived test objects can be restored if needed. To restore a test object, go to the archived test objects list, select the test object you want to restore, and click the "Restore" button. This will make the test object active again and available for use in tests.