Directional RCD

Some RCD devices are directional. This has no effect on the direction of current sensing, but is a limitation on the installation.
Directional RCD devices contain electronics on one side of the switching element, a trip event should also disconnect the internal electronics.

Should you experience difficulties testing these RCD devices with the EST, verify if the line and load connections are wired to their correct sides in your testobject.

note

Most type B devices are directional and need to be installed with the correct line and load orientation.

tip

Directional RCD devices cannot withstand a insulation test between phases and neutral due to active electronics.
Enable the insulation only test to earth option when these devices are present in your test object.

ETI KZS Series​

An example of such device is the ETI KZS series.

When these trigger, their trip mechanism activates a high current pulse is generated.
On incorrect wiring, with the electronics on the line side of the device, the electronics are not disconnected and the trip current continues.
This may result in a high current flowing through the upstream protection, possibly causing it to activate.

ETI KZS Series

Source: ETI KZS Series datasheet